Configurable number of modules and slots
Up to 73 byte of process data* per direction when Datamapper is chosen
input data, output data, ioxs, status information (optional generic data provider, optional apdu status)
direction of output data is limited to 69 byte when optional generic data provider is used
up to 1 ms cycle time
Up to 1434 byte of process data per direction when RPC transport is chosen
cycle time must not be less then 100ms
Support for process alarms
Support for record data (read, write), where a maximum of 1116 byte can be accessed in each direction
Support for Redundancy (MRP) (FW Rev. 2.1)
Dynamic module configuration (provided by connection request from PLC) for modules mapped to the cyclic channel (FW Rev. 2.1)
Info |
---|
*IOXS will take one byte additionally to each mapped submodule |
What functionality is not supported?
...